Zero Halogen, Low
Smoke (OHLS®) coaxial cable for visual safety
systems.

Fire resistant 75Ω Coax
similar to RG59. Ideal for CCTV, security, smoke
detection and evacuation monitoring applications,
where continued functionality is required during
a fire situation. Due to the zero halogen low
smoke construction Firetuf Coaxial is ideal
for use in public, commercial and industrial
environments.
| Construction |
|
 |
| Conductor: |
|
Plain annealed copper
wire. |
| Insulation: |
|
Dual layer Polyethylene
and Silicone rubber. |
| Binder: |
|
Close weave glass
tape. |
| Screen: |
|
Two layers plain
copper wire braid. |
| Sheath: |
|
Thermoplastic Zero
Halogen Low Smoke (OHLS®) compound. |
| Physical
Characteristics |
|
 |
| Min. bending
radius: |
|
Installation: 10
x overall diameter. Fixed: 5 x overall diameter. |
| Temperature
range: |
|
Installation: -5ºC
to +60ºC. Operating: -30ºC to +70ºC |
| Conductor
Diameter: |
|
0.65mm. |
| Overall
Diameter: |
|
9.1mm |
| Approximate
weight: |
|
110 kg/km |
| Electrical
Characteristics @ 20ºC |
| Character
impedance: |
|
|
|
Ω(ohms) |
|
75±5 |
| Attenuation
at (nominal): |
|
0,5Mhz |
|
dB/100m |
|
0.65 |
| |
|
1Mhz |
|
dB/100m |
|
0.90 |
| |
|
5Mhz |
|
dB/100m |
|
2.24 |
| |
|
10Mhz |
|
dB/100m |
|
3.35 |
| |
|
100Mhz |
|
dB/100m |
|
15.03 |
| |
|
300Mhz |
|
dB/100m |
|
32.51 |
| Screening
Attenuation : |
|
30-1000Mhz |
|
dB |
|
>100 |
| |
|
1000-2000Mhz |
|
dB |
|
>95 |
| |
|
2000-3000Mhz |
|
dB |
|
>89 |
| Transfer
impedence: |
|
5-30Mhz |
|
mΩ/m |
|
≤5 |
| |
|
Velocity ratio |
|
% |
|
61.4 |
| |
|
DC resistance |
|
|
|
|
| |
|
Inner conductor |
|
Ω/km |
|
55.3 |
| |
|
Outer conductor |
|
Ω/km |
|
3.7 |
| |
|
Return loss |
|
|
|
|
| |
|
5-30Mhz |
|
dB |
|
>22 |
| |
|
30-470Mhz |
|
dB |
|
>22 |
| |
|
470-1000Mhz |
|
dB |
|
>18 |
| |
|
1000-3000Mhz |
|
dB |
|
>20 |
| |
|
Electrical
strength(1min.) |
|
|
|
|
| |
|
Dielectric |
|
kV d.c. |
|
2.00 |
| |
|
Sheath |
|
kV d.c. |
|
3.75 |
| Standards
Achieved |
|
 |
| Construction: |
|
BS EN 50117-1 &
draft BS EN 50117-2-4 2002,
EN 50083-2/A1 screening class A |
| Circuit
integrity: |
|
BS 5839-1:2002 Clause
26.2e Enhanced
BS 8434-2:2003
BS EN 50200 >PH120
IEC 60331-23 |
| Flame propagation: |
|
IEC 60332-3 |
| Acid gas
emission: |
|
IEC 60754 |
| Smoke emission: |
|
IEC 601034 |

Download Firetuf Cables Brochure

For further information and supply of Draka FireTuf Coaxial cable please contact:
FS Cables
01727 828 828
FTD@fscables.com |