Circuit Integrity
Structured Wiring Alarm cable. Compatible with
all known connection systems according to EN
50173.

Based on the design for structured
wiring (found in IEC 61156 and BS EN 50288),
Firetuf Data cable brings together high frequency
data transmission and circuit integrity in a
one pair, two pair and four pair cable that
will continue to transmit data even when being
directly attacked by fire.
Firetuf Data has successfully
passed BS 5839: 2002 test protocols. This patented
design allows the continuation of data transmission
in the event of a fire.
Firetuf Data has three designs:
one, two and four pair construction all using
the same wire size of 0.63mm, overall screened
plus a drain wire and braided.
| Physical
Characteristics |
|
 |
| Min. Installation
Bend Radius: |
|
8 x Dia. |
| Min. Fixed
Bending Radius: |
|
6 x Dia. |
| Installation
Temp. Range: |
|
0°C to 50°C. |
| Installed
Operating Temp. Range: |
|
-20°C to 60°C. |
| Electrical
Characteristics @20ºC |
|
 |
| Structural
Return Loss Rl: |
|
>IEC
dB. |
| Characteristic
Impedance @10MHz: |
|
100±5Ω. |
| DC
Conductor Loop Resistance: |
|
<19Ω/100m. |
| Max. Resistance
unbalance: |
|
≤2%. |
| Nominal
Velocity of Propagation: |
|
57%. |
| Max. Capacitance
unbalance: |
|
1600 pF/km. |
| Insulation
Resistance (500V): |
|
≥5000 MΩ.km. |
| Standards
Achieved |
|
 |
| ISO/IEC
11801:1994; EN 50173:1995; EN 50288-2-1 |
| Circuit
Integrity: |
|
BS 5839-1:2002 Clause
26.2e Enhanced
BS 8434-2:2003
BS EN 50200 >PH120
IEC 60331-23
BS 6387 C |
| Flame propagation: |
|
UL 1581 VW1; IEC
60332.3 |
| Acid gas
emission: |
|
IEC 60754 |
| Smoke emission:
|
|
IEC 61034 |
|
Cable |
Part
No. |
Nominal
Diameter (mm) |
Approx.
Weight (Kg/Km) |
1
pair |
910234 |
6.8 |
48 |
2
pair |
910244 |
8.1 |
97 |
4
pair |
910245 |
10.45 |
122 |
More detailed data sheets
available upon request.

Download Firetuf Cables Brochure

For further information and supply of Draka FireTuf Data cable please contact:
FS Cables
01727 828 828
FTD@fscables.com |