Firetuf FT30
Firetuf FT120
Firetuf FTEMC
Firetuf FTP120
Firetuf FTP
Firetuf FT Sifer
Firetuf FT Data
Firetuf FT Coaxial
Firetuf FT Connecta

Circuit Integrity Structured Wiring Alarm cable. Compatible with all known connection systems according to EN 50173.

Firetuf Plus Enhanced

Based on the design for structured wiring (found in IEC 61156 and BS EN 50288), Firetuf Data cable brings together high frequency data transmission and circuit integrity in a one pair, two pair and four pair cable that will continue to transmit data even when being directly attacked by fire.

Firetuf Data has successfully passed BS 5839: 2002 test protocols. This patented design allows the continuation of data transmission in the event of a fire.

Firetuf Data has three designs: one, two and four pair construction all using the same wire size of 0.63mm, overall screened plus a drain wire and braided.

Physical Characteristics  
Min. Installation Bend Radius:   8 x Dia.
Min. Fixed Bending Radius:   6 x Dia.
Installation Temp. Range:   0°C to 50°C.
Installed Operating Temp. Range:   -20°C to 60°C.

Electrical Characteristics @20ºC  
Structural Return Loss Rl:   >IEC dB.
Characteristic Impedance @10MHz:   100±5Ω.
DC Conductor Loop Resistance:   <19Ω/100m.
Max. Resistance unbalance:   ≤2%.
Nominal Velocity of Propagation:   57%.
Max. Capacitance unbalance:   1600 pF/km.
Insulation Resistance (500V):   ≥5000 MΩ.km.

Standards Achieved  
ISO/IEC 11801:1994; EN 50173:1995; EN 50288-2-1
Circuit Integrity:   BS 5839-1:2002 Clause 26.2e Enhanced
BS 8434-2:2003
BS EN 50200 >PH120
IEC 60331-23
BS 6387 C
Flame propagation:   UL 1581 VW1; IEC 60332.3
Acid gas emission:   IEC 60754
Smoke emission:   IEC 61034

Cable
Part No.
Nominal Diameter (mm)
Approx. Weight (Kg/Km)
1 pair
910234
6.8
48
2 pair
910244
8.1
97
4 pair
910245
10.45
122

More detailed data sheets available upon request.

Download Firetuf Cables Brochure

For further information and supply of Draka FireTuf Data cable please contact:

FS Cables
01727 828 828
FTD@fscables.com