Firetuf Easystrip
Zero Halogen Low Smoke cable has been designed
and manufactured in the UK to provide superior
flame retardance and circuit integrity, together
with optimised ease of installation characteristics.
Manufactured to BS7629-1 and meeting the Standard
category of BS 5839-1:2002. Tested and approved
by LPCB and BASEC.

• Fastest ever sheath removal,
allowing reduced termination times
• Smallest diameter and most flexible
• Easily dressable
• Smallest bending radius without deformation
or cable kinking
• Reduced weight
• Twisted core construction to improve
signal clarity
• Suitable for use in Zone 1 and Zone 2
hazardous areas
| Construction |
|
 |
| Conductors: |
|
Solid or stranded
plain annealed copper wire. |
| Insulation: |
|
Silicone
rubber. |
| Electrostatic
screen: |
|
Aluminium/polyester
laminated tape. |
| Conductor
(earth): |
|
Solid or stranded
tinned annealed copper. |
| Sheath: |
|
High performance,
Thermoplastic Zero Halogen, Low Smoke
(OHLS®) compound. |
| Physical Characteristics |
|
 |
| Voltage rating (Uo/U): |
|
300/500V. |
| Operating temp: |
|
-40°C to +90°C
(The cable should not be flexed when
either the ambient or cable temperature
is below 0°C). |
| Min. bending radius: |
|
6 x overall diameter of cable. |
| Standards
Achieved |
|
 |
| Circuit integrity |
|
BS 5839-1:2002 Clause
26.2d Standard.
BS 8434-1:2003.
BS EN 50200 PH30.
BS 6387 C, W & Z. |
| Flame propagation: |
|
IEC 60332-3, IEC
60332-1, BS EN 50265, BS EN 50266. |
| Acid gas emission: |
|
IEC 60754, BS EN
50267. |
| Smoke emission: |
|
IEC 61034, BS EN
50268. |


Download Firetuf Cables Brochure |