Zero Halogen, Low Smoke (OHLS®) cable with stranded copper conductors and a protective armour layer. Manufactured to BS 7846. Tested and approved by LPCB and BASEC.

Firetuf Plus Enhanced

These cables offer the advantages of an armoured 600/1000 Volt rated, zero halogen, low smoke cable with circuit integrity. They are intended for use in installations where vital circuits are required to continue operation in the event of the outbreak of fire. Firetuf Power is particularly suited for use in public buildings and constructions (such as hospitals, theatres, shopping developments, tunnels, mass transit railways, oil & petrochemical plants, power stations and computer installations) where the danger to life, equipment and structures may be greatly increased in the event of a power failure due to fire.


Also available in unarmoured design. Details available upon request.

Construction  
Conductors:   Plain annealed stranded copper conductors. For sizes up to and including 35mm2 these are circular. Shaped conductors start at 50mm2 with the exception of 2 core cables where shaped conductors start at 25mm2.
Insulation:   Mica-glass fire-resistant tapes, covered by an extruded layer of cross-linked polyethylene.
Binder:   Polyester tape.
Bedding:   An extruded layer of Zero Halogen, Low Smoke (OHLS®) compound.
Armour:   Single layer of galvanised steel wires.
Sheath:   Thermoplastic Zero Halogen, Low Smoke (OHLS®) compound.

Physical Characteristics  
Voltage rating (Uo/U):   600/1000V.
Operating temp:   -40°C to +90°C (The cable should not be flexed when
either the ambient or cable temperature is below 0°C).
Min. bending radius:   8 x overall diameter of cable.
Note: In the event of a fire, the increase in impedance may require consideration to the installation of larger conductor sizes, to accommodate motor starting loads and the performance of protective conductors.

Standards Achieved  
Circuit integrity   IEC 60331, BS 7846 F2, BS 6387 categories C, W & Z.
Acid gas emission:   IEC 60754, BS EN 50267.
Flame propagation:   IEC 60332-3, BS EN 50265, BS EN 50266.
Smoke emission:   IEC 61034, BS EN 50268.

 

Firetuf Power Technical Data