Low Voltage Cables
YY OHLS
6491B
624-BH
3183B
694-LSH
6945LS7W to 69448LS7W

 

624-BH - Premium Fire Safety Wiring Cable

XLPE Insulated and OHLS® Sheathed Flat Wiring Cables
With Bare CPC

STANDARD: BS 7211

VOLTAGE RATING: 300/500V

APPLICATION: Domestic and light industrial wiring, where smoke and acid gas emission would pose a major hazard in the event of fire. Can be clipped to surface, on trays or in free air where there is little risk of mechanical damage. Suitable for laying into trunking or conduit etc. when mechanical protection is required. May be embedded in plaster or laid in walls.

CONSTRUCTION: Two or three core flat cables with an additional uninsulated copper circuit protective conductor. Solid or stranded plain copper conductors. XLPE insulated, laid parallel with CPC and Zero Halogen Low Smoke (OHLS®) sheathed.

CORE COLOURS:
Two core: Brown and Blue.
Three core: Brown, Black and Grey.

SHEATH COLOUR: White

BASEC: Certified

MAXIMUM CONDUCTOR TEMPERATURE: 90ºC
Note: Where a conductor operates at a temperature exceeding 70ºC it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see regulation 512-02 of BS7671, the 16th Edition of IEE Wiring Regulations)

CURRENT RATING: Refer to table 4D5A in BS7671 or refer to “A Closer Look at Cable”

FIRE PERFORMANCE CHARACTERISTICS:
Smoke emission: IEC 61034 , BS EN 50268
Acid gas emission: IEC 60754-2, BS EN 50267-2
Flame propagation: IEC 60332-1, BS EN 50265

* Stranded Class 2 cpc

 