Low Voltage Cables
Saffire Swiftfit
6491B
624-BH
3183B
694-LSH
6945LS7W to 69448LS7W

 

694-LSH - Premium Fire Safety Energy Cable

XLPE Insulated, OHLS® Bedded, Armoured and OHLS® Sheathed Cables With Stranded Copper Conductors

STANDARD: BS 6724

VOLTAGE RATING: 600/1000V

APPLICATION: Industrial wiring and mains distribution, where smoke and acid gas emission would pose a major hazard in the event of fire. Can be laid direct in the ground, or in ducts, clipped to surface, on trays or in free air. May be embedded in concrete.

CONSTRUCTION: Single, Two, Three, Four and Five core cables. Stranded plain copper conductors, XLPE insulated, cores laid up, extruded Zero Halogen, Low Smoke (OHLS®) bedding, galvanised steel wire armoured (Aluminium wires for single cores) and Zero Halogen, Low Smoke (OHLS®) sheathed.

CORE COLOURS:
Single core: Brown or Blue.
Two core: Brown and Blue.
Three core: Brown, Black and Grey.
Four core: Brown, Black, Grey and Blue.
Five core: Brown, Black, Grey, Green/Yellow and Blue.

SHEATH COLOURS: Black. Other colours available to order.

BASEC: Certified

MINIMUM BENDING RADIUS: 6D circular conductors. 8D shaped conductors.

MAXIMUM CONDUCTOR TEMPERATURE: 90°C.
Note: Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see regulation 512-02 of BS7671, the 16th Edition of IEE Wiring Regulations)

CURRENT RATING: Refer to table 4E4A or 4E4B of BS7671, ERA69-30 Pt. V or “A Closer Look at Cable”

FIRE PERFORMANCE CHARACTERISTICS:
Smoke emission: IEC 61034 , BS EN 50268
Acid gas emission: IEC 60754-1, BS EN 50267
Flame propagation: IEC 60332-1, IEC 60332-3, BS EN 50265, Categories C & A; BS EN 50266.

Shaped conductors unless otherwise stated.
* Circular, non-compacted, conductors. # Compacted circular conductors.