Low Voltage Cables
Saffire Swiftfit
6491B
624-BH
3183B
694-LSH
6945LS7W to 69448LS7W

 

6945LS7W TO 69448LS7W - Premium Fire Safety Multicore Auxilliary Cable

XLPE Insulated, OHLS® Bedded,Armoured and OHLS® Sheathed. Multicore Control Cables With Stranded Copper Conductors

STANDARD: BS 6724

VOLTAGE RATING: 600/1000V

APPLICATION: Industrial wiring for remote control and telemetry circuits etc. where smoke and acid gas emission would pose a major hazard in the event of fire. Can be laid direct in the ground, or in ducts, clipped to surface, on trays or in free air. May be embedded in concrete.

CONSTRUCTION: Multi-core cables. Stranded plain copper conductors, XLPE insulated, cores laid up, extruded Zero Halogen, Low Smoke (OHLS®) bedding, galvanised steel wire armoured and Zero Halogen Low Smoke (OHLS®) sheathed

CORE COLOURS: White with Black numerals.

SHEATH COLOURS: Black. Other colours available to order.

BASEC: Certified

MINIMUM BENDING RADIUS: 6D

MAXIMUM CONDUCTOR TEMPERATURE: 90°C.
Note: Where a conductor operates at a temperature exceeding 70°C it shall be ascertained that the equipment connected to the conductor is suitable for the conductor operating temperature (see regulation 512-02 of BS7671, the 16th Edition of IEE Wiring Regulations)

CURRENT RATING: Available upon request.

FIRE PERFORMANCE CHARACTERISTICS:
Smoke emission: IEC 61034 , BS EN 50268
Acid gas emission: IEC 60754-1, BS EN 50267
Flame propagation: IEC 60332-1, IEC 60332-3, BS EN 50265, Categories C & A; BS EN 50266.