Special Cables
HITUF
PWO1
HO7RN-F
SY Control
YY and CY Control
3183Y - Arctic
NYM-J / NYM-O
Type 8, Type 16
CAT 5E
CAT 6
TV 4425
BS 6622

 

 

97HUF - HITUF Energy Cable

XLPE Insulated, PVC Inner Sheath High Impact Resistant PVC Sheath

STANDARD: Draka

VOLTAGE RATING: 600/1000V

APPLICATION: Industrial wiring and mains distribution. Particularly suitable for warehousing, golf courses, flood lighting, farms, water works and gantry wiring. Suitable clipped direct on tray, buried in concrete and in ducting. Must be mechanically protected when buried in the ground (Ref. BS7671 522-06-03)

CONSTRUCTION: Three and four core plain copper stranded conductors, XLPE insulation, PVC inner covering, high impact PVC sheath

CORE COLOURS:
Three core: Green/Yellow, Blue and Brown.
Four core: Green/Yellow, Brown, Blue and Grey.

SHEATH COLOUR: Black

MINIMUM BENDING RADIUS: 6D

MAXIMUM CONDUCTOR TEMPERATURE: 70°C

CURRENT RATING: Refer to tables 4D2A and 4D2B in BS7671 or “A Closer Look at Cable”

CABLE ACCESSORIES
Nylon glands: HITUF® cables can be terminated using impact resistant nylon glands fitted with a nitrile rubber bush to provide weatherproof entry. Where these cables are to be installed in Zone 1 and Zone 2 fire risk areas, a flame proof gland should be used.
Nylon cable clip: These clips are impact resistant, weatherproof and resistant to a wide range of chemical attack. The interior edges are radiused.

Download Product Brochure