Special Cables
318-Y
309-Y

 

 

BS 6622 - Power Distribution MV Cables

STANDARD: BS 6622

VOLTAGE RATING: 6350/11000V

APPLICATION:
Power cables for power networks, underground, outdoors and in cable ducting.

CONDUCTOR SCREEN:
Extruded Semi Conducting Layer

INSULATION SCREEN:
Extruded Semi Conducting Layer and Copper Tape Screen.

INSULATION: XLPE (Type GP8 to BS7655)

BEDDING: PVC (Type 9 to BS7655)

ARMOURING:
Single core - aluminium wire armoured (AWA)
Multicore - Steel Wire Amoured (SWA)

SHEATH: PVC (Type 9 to BS7655), red

MINIMUM BENDING RADIUS: 13D

MAXIMUM CONDUCTOR TEMPERATURE: 90°C
OHLS bedded and sheathed cables to BS7835 are available upon request.

Download Product Brochure