Firetuf FT L-SIFER
London Underground Fire Resistant Single Core Cable
Firetuf FT L-Sifer is a fire resistant, zero halogen and low smoke (OHLS®) single core cable designed to maintain circuit integrity during a fire and is approved by LUL for above and below ground use.
L-Sifer is ideally suited to drawing into conduit installations that provide adequate mechanical protection and it forms the key part of a wiring system for evacuation and fire fighting applications.
Conductors: |
Stranded plain annealed copper wire (class 2) to BS EN 60228 |
Insulation: |
Comprises mica-glass fire resistant tape covered by an extruded layer of cross-linked Zero Halogen, Low Smoke (OHLS®) compound |
Voltage rating (U0/U): |
600/1000V |
Operating temp |
-25°C to +90°C
(the cable should not be installed when either the ambient or cable temperature is below 0°C) |
Min, bending radius |
8 x overall diameter of cable |
Curent rating |
Refer to tables 4E1A & 4E1B in BS7671 |
General performance |
Complies with LU specification 1-085 |
Circuit integrity |
BS 6387 categories C, W and Z (when tested in steel conduit).
Exceeds IEC 60331-21 3 hours at 750°C (test temperature is increased to 950°C, equivalent to BS 6387 category C) |
Smoke emission |
LU 1-085 A3
BS EN 61034-2 |
Acid gas emmision |
LU 1-085 A3
BS EN 50267-2-1 |
Flame propagation |
LU 1-085 A3
BS EN 60332-1-2
BS EN 60332-3-* |
FT L-Sifer Datasheet
- [548 KB]